Model Type |
SMART KING RM |
 |
Model Name |
SMK-1500A-RM |
 |
 |
AC INPUT
|
 |
AC Input Capacity on Battery |
1500VA |
 |
AC Input Voltage |
(+/-) 25% at line
input |
 |
AC Input Frequency |
50 or 60 Hz+/-5Hz
(auto sensing) |
 |
AC Input Phase |
Single |
 |
 |
AC OUTPUT
|
 |
AC Output Voltage |
Pure sine wave at
+/-5% of nominal, -10% of nominal after low battery warning |
 |
AC Output Frequency |
50 or 60 Hz +/- 0.5% |
 |
AC Output Voltage Regulation |
AVR automatically
increase output voltage 15% above input voltage if -9% to -25%
of nominal. AVR decrease output voltage 15% below input voltage
if +9% to +25% of nominal |
 |
 |
PROTECTION
|
 |
Protection Spike |
320 Joules, 2ms |
 |
Protection EMI/RFI |
10dB at 0.15 MHz, 50
dB at 30 MHz |
 |
Protection Overload |
UPS automatic
shutdown if overload exceeds 110% nominal at 20 sec and 125% at
5 sec |
 |
Protection Unit |
Fuse for 110V models
(600VA~2500VA) and 220V models (under 1250VA), breaker for 110V
model (3000VA) and 220V models (above 1500VA) |
 |
Protection Transfer Time |
2/4 milliseconds
(typical), including detection time |
 |
Protection Short Protection |
UPS output cut off
immediately or input fuse( or breaker) protection |
 |
 |
BATTERY
|
 |
Battery Type |
Hot swappable,
sealed, maintenance-free lead acid, with 3 - 6 year lifetime |
 |
Battery Typical |
4 hours (to 90% of
full capacity) |
 |
Battery Protection |
Automatic self-test
& discharge protection, replace battery indicator |
 |
Battery Run Time |
90 minutes |
 |
 |
PHYSICAL
|
 |
Physical Weight lbs Tower |
N/A |
 |
Physical Weight kgs RM |
26.1 |
 |
Physical Weight lbs RM |
(57.4lb) |
 |
Physical Dimension mm Tower |
N/A |
 |
Physical Dimension inch Tower |
N/A |
 |
Physical Dimension mm RM |
483x381x130 |
 |
Physical Dimension inch RM |
(19.0 |
 |
 |
INDICATOR
|
 |
LCD Indicators Status |
Indicate line,
bypass, inv, backup, fault, bat capacity, load capacity, I/P
frequency, O/P voltage, O/P frequency, inside temperature, fault
status, load |
 |
LED |
LED |
 |
 |
ALARM
|
 |
Alarm Battery Backup |
Slow beeping sound
(about 0.25 Hz) |
 |
Alarm Battery Low |
Rapid beeping sound
(about 1.00Hz) |
 |
Alarm Overload |
Continue beeping
sound |
 |
 |
INTERFACE
|
 |
Interface Dry Contact |
Sends AC fail and
battery low signals, and receives shutdown signal from computer |
 |
Interface RS-232 |
Detect battery low,
Schedule UPS on/off, AC input/output power status display |
 |
Interface Option |
Novell, SNMP,
Windows NT, Window 95/98/2000/ME/XP |
 |
 |
ENVIRONMENT
|
 |
Environment Ambient |
3,500 meters max.
elevation, 0-95% humidity non-condensing, 0-48 deg c |
 |
Environment Audible |
<40dBA (1 meter from
surface) |
 |
Environment Storage Condition |
15,000 meters max.
elevation |
 |
ShowOrder |
50 |
|