100V or
110V/115V/120V or 220V/230V/240V +/- 25% at line input
AC Input Frequency
50 or 60 Hz+/-5%
(auto sensing)
AC Input Transfer
N/A
AC OUTPUT
AC Output Voltage
Simulated sine wave
at 100V or 110V/115V/120V or 220V/230V/240V +/- 25%
AC Output Frequency
50 or 60 Hz +/- 0.5%
AC Output Voltage Regulation
AVR automatically
increase output voltage 15% above input voltage if -9% to -25%
of nominal. AVR decrease output voltage 13% below input voltage
if +9% to +25% of nominal
AC Output Transfer
2/4 milliseconds,
including detection time
PROTECTION
Protection Spike
480 Joules / 2ms
Protection Overload
UPS automatic
shutdown if overload exceeds 110% nominal at 60 sec and 130% at
3 sec
Protection Unit
Fuse for overload &
short circuit protection
Protection Inside Protection
UPS output cut off
immediately or input fuse protection
BATTERY
Battery Type
UPS output cut off
immediately or input fuse protection
Battery Typical
6 hours (to 90% of
full capacity)
Battery Protection
Auto discharge
protection
Battery Run Time
70 - 80 minutes
PHYSICAL
Physical Weight kgs
13.4
Physical Weight lbs
29.5
Physical Shipping Weight kgs
14.8
Physical Shipping Weight lbs
32.6
Physical Dimension mm
15 x 15.12 x 7.56
Physical Dimension inch
15.0
INDICATOR
LED
LED
ALARM
Alarm Battery Backup
Slow beeping sound
(about 0.47 Hz)
Alarm Battery Low
Rapid beeping sound
(about 1.82Hz)
Alarm Overload
Continue beeping
sound
INTERFACE
Interface RS-232
YES
ENVIRONMENT
Environment Ambient
3,500 meters max.
elevation, 0-95% humidity non-condensing, 0-40 deg c